Condor 415U-1-Cx Battery Powered Wireless IO
Version 1.4
24
Sens
Sensitivity value (float) which is configured to the value of
change that will trigger a transmitted event.
Raw
Raw sensor data value as read
Value
Scaled using Range/Offset, sensor data value that is
transmitted.
Modbus IO Points Menu:
a) Select SDI-12 or Modbus:
Modbus
Enable Modbus or SDI-12 smart sensor configuration.
Default is Modbus.
Note: If there is a configuration for
SDI-12 or Modbus, then user must delete all
configuration before switching or removing.
b) Add IO Point
Configure new Modbus input mapping.
c) Sampling / Warmup Time
Configure the Modbus sensor sample and warmup time.
Warmup is used to allow the sensor to stabilize before a
poll is performed.
d) Modbus Serial Config
Setup of the Modbus serial setting for baud rate, stop bits,
parity and number of data bits. Default is 9600, 8, N, 1
e) Force Modbus Poll
Force a poll of all configured mappings as in menu below.
f) Slave ID# 2: REG 10001 (FC
2:00000), AP REG 15513
Example mapping reading from slave ID 2, Modbus
register 10001 (discrete input 1) which is sent to AP
register 15513. Selecting this menu item will open a new
menu to edit mapping. See below.
g) Slave ID# 2: REG 30010 (FC
4:00009), AP REG 35001
h) Slave ID# 2: REG 10004 (FC
2:00003), AP REG 40001
l) Return to Main menu
Return to main menu.
Modbus mapping menu item can be selected from menu above to allow changes to be made to
individual parameters after initial configuration.
Modbus IOs
REG
15513
Format
U-2
Range
0
Offset
0
Sens
1
Display
-
Raw
Value
ON
Slave ID# 2: REG 10001 (FC 2:00000), AP REG 15513 Menu:
a) AP REG
Change AP destination Register
b) Report Format
Change the Reporting format
c) Span / Range
Change Span / Range
d) Zero / Offset
Change Zero / Offset
e) Display Units
Change Display Units
f) Display Scaling
Change Scaling
g) Report Sensitivity
Change Sensitivity
h) Slave ID
Change Slave ID
i) Slave Register/Function Code:Address
Change Function Code or
Address
j) Remove IO
Remove the Poll mapping
k) Save Config
Save configuration
l) Return to previous menu
Return to previous menu