User Manual
Condor 415U-1-Cx Battery Powered Wireless IO
Version 1.4
23
SP1
SP REG
15501
ON Def
On
OFF Def
On
ON REG
35502
OFF REG 35501
AN1 Set Point Menu:
a) Set Point Value REG
Sets the discrete input register
b) ON Level Default
Sets the default value for ON level as a percentage of full scale
c) OFF Level Default
Sets the default value for OFF level as a percentage of full
scale
d) ON Level Control REG
Sets the register that holds the ON value as a percentage of
full scale. The value written to the register is stored with two
fixed decimal places, eg: 10.5% use value of 1050
e) OFF Level Control REG
Sets the register that holds the OFF value as a percentage of
full scale. The value written to the register is stored with two
fixed decimal places, eg: 85.23% use value of 8523
f) Return to Main menu
Modbus Slave Smart Sensor
Note: supported in R1.7 or later firmware
Smart sensors using either SDI-12 or Modbus can be connected, and values can be transmitted
through the Condor wireless network. This section describes the configuration of the Modbus master
gateway to be able to poll slave devices, such as pressure or level transducers and read field values.
A Modbus mapping in required to be configured for each sensor input value. This mapping defines the
Modbus ID, register address, value format and the AP register address that the value will be sent to.
Each mapping when configured will be added to the config menu to allow later editing if required.
Each of these mappings once setup will be polled based on the configured sample time and there is a
configurable sensor warmup time to allow the Modbus sensor values to stabilize after power on
before sampling.
Modbus slave poll timeout is fixed to 5 seconds and the number of retries is fixed to 3 for all slave
devices.
There is no limitation of the number of connected slave devices, but there is a limitation on the
number of sensor inputs. The maximum number that can be configured is 46, not including the fixed
discrete, analog and internal inputs.
To configure the Modbus gateway from the main menu, select the I/O Setup and then select Smart
Sensor menu item.
Smart sensor menu will be displayed as below:
Modbus IOs
REG
15513
35001
40001
AP registers that sensor inputs are transmitted to.
Format U-2
U-4
F-4
Data type: Unsigned int or float in 1-, 2- and 4-byte
formats. 4 Byte formats can also be adjusted for word
order, most significant or least significant word first.
Range
Scaling value range or span
Offset
Scaling value offset or zero