User Manual
Condor 415U-1-Cx Battery Powered Wireless IO
Version 1.4
10
Installation
Enclosure
ELPRO 415U-1-Cx electronics and battery are enclosed in a rugged IP66 rated cast Aluminium 190mm
x 197mm enclosure with an opening/removable door.
Sensor and power connections are made through cable entry glands into internal industrial push
connect wiring terminals.
It is suitable to be installed in a variety of situations such as outdoor, indoor, and cabinet installations
and has the ability to be secured with padlock if required.
Mounting options are
•
Standard panel mounting via M6 mounting Holes 176mm x 119mm square provide by
integrated mounting feet on the enclosure
•
Pole or Rail (horizontal or vertical) mounted using an aluminium mounting plate and either
Standard U clamps or s/s cable ties.
Grounding
To provide maximum surge and lightning protection for antenna connection
and sensor inputs, each module should be effectively earthed/grounded via
a GND terminal on the module. This is to ensure that the surge protection
circuits inside the module are effective.
If the 415U-1-Cx is to be mounted in an enclosure you need to ensure the
enclosure ground and the antenna mast/pole ground are connected to the
same common ground point to avoid lightning surges.
The 415U-1-Cx has a dedicated earth/ground connection M5 x 0.8 screw on
the side of the enclosure for this Earth connection. All earth/ground wiring
should be minimum 18 AWG (2 mm2),. Earth screw maximum length is 10mm.
Recommended installation earthing for outdoor installation is outline in diagram.