5-17
PERFORMANCE DATA & PRESSURE CURVES
Revision Y06-02
Service Manual - KN Series
5.12
KN36 / OU10-36T R410A
5.12.1
Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OD COIL (
°
C)
DATA
ENTERING AIR WB/DB ID COIL (
°
C)
15/21
17/24
19/27
21/29
23/32
15
(1)
TC
10.22 10.59 10.84 11.10 11.26
SC
6.35 6.62 6.88 7.05 7.18
PI
2.37 2.37 2.38 2.38 2.40
20
(1)
TC
9.89 10.43 10.76 11.01 11.25
SC
6.22 6.56 6.83 7.03 7.16
PI
2.57 2.58 2.59 2.60 2.61
25
TC
9.36 10.10 10.62 10.95 11.21
SC
6.06 6.43 6.78 6.98 7.11
PI
2.78 2.80 2.82 2.83 2.85
30
TC
8.75 9.53 10.29
10.66
10.98
SC
5.87 6.24 6.63 6.83 6.96
PI
3.00 3.04 3.07
3.09 3.12
35
TC
8.10 8.79
9.70
10.19 10.67
SC
5.58 5.98
6.48
6.67 6.80
PI
3.23 3.29
3.34
3.37 3.38
40
TC
7.37 8.02 8.75
9.57 10.06
SC
5.26 5.66 6.13 6.32 6.45
PI
3.49 3.54 3.60 3.65 3.68
46
TC
6.39 6.99 7.69 8.49 9.15
SC
4.85 5.19 5.59 5.78 5.91
PI
3.81 3.87 3.96 4.01 4.06
LEGEND
TC –
Total Cooling Capacity, kW
SC – Sensible
Capacity,
kW
PI –
Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OD –
Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).
Summary of Contents for KN 24 RC
Page 50: ...9 2 REFRIGERATION DIAGRAMS Revision Y06 02 Service Manual KN Series 9 1 2 KN 30 R410A...
Page 51: ...9 3 REFRIGERATION DIAGRAMS Revision Y06 02 Service Manual KN Series 9 1 3 KN 36 R410A...
Page 52: ...9 4 REFRIGERATION DIAGRAMS Revision Y06 02 Service Manual KN Series 9 1 4 KN 36T R410A...
Page 53: ...9 5 REFRIGERATION DIAGRAMS Revision Y06 02 Service Manual KN Series 9 1 5 KN 45T R410A...
Page 57: ...11 2 CONTROL SYSTEM Revision Y06 02 Service Manual KN Series 11 1 3 Main PCB Controller...