5-13
PERFORMANCE DATA & PRESSURE CURVES
Revision Y06-02
Service Manual - KN Series
5.9
KN36 / OU10-36 R410A
5.9.1
Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OD COIL (
°
C)
DATA
ENTERING AIR WB/DB ID COIL (
°
C)
15/21
17/24
19/27
21/29
23/32
15
(1)
TC
10.65 11.03 11.29 11.55 11.73
SC
6.74 7.03 7.30 7.48 7.62
PI
2.47 2.47 2.48 2.48 2.50
20
(1)
TC
10.30 10.86 11.20 11.46 11.71
SC
6.60 6.96 7.26 7.46 7.60
PI
2.68 2.69 2.70 2.71 2.72
25
TC
9.74 10.52 11.06 11.40 11.67
SC
6.43 6.83 7.20 7.41 7.54
PI
2.89 2.91 2.93 2.95 2.97
30
TC
9.11 9.92 10.72
11.10
11.43
SC
6.23 6.62 7.04 7.25 7.39
PI
3.12 3.17 3.20
3.22 3.25
35
TC
8.44 9.16
10.10
10.61 11.11
SC
5.93 6.35
6.88
7.08 7.22
PI
3.37 3.42
3.48
3.51 3.53
40
TC
7.67 8.35 9.11
9.97 10.48
SC
5.59 6.01 6.51 6.71 6.85
PI
3.63 3.69 3.75 3.80 3.84
46
TC
6.66 7.28 8.00 8.84 9.53
SC
5.14 5.51 5.93 6.14 6.28
PI
3.97 4.03 4.12 4.18 4.23
LEGEND
TC –
Total Cooling Capacity, kW
SC – Sensible
Capacity,
kW
PI –
Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OD –
Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).
Summary of Contents for KN 24 RC
Page 50: ...9 2 REFRIGERATION DIAGRAMS Revision Y06 02 Service Manual KN Series 9 1 2 KN 30 R410A...
Page 51: ...9 3 REFRIGERATION DIAGRAMS Revision Y06 02 Service Manual KN Series 9 1 3 KN 36 R410A...
Page 52: ...9 4 REFRIGERATION DIAGRAMS Revision Y06 02 Service Manual KN Series 9 1 4 KN 36T R410A...
Page 53: ...9 5 REFRIGERATION DIAGRAMS Revision Y06 02 Service Manual KN Series 9 1 5 KN 45T R410A...
Page 57: ...11 2 CONTROL SYSTEM Revision Y06 02 Service Manual KN Series 11 1 3 Main PCB Controller...