20
TEST OPERATION
1. The test operation must be carried out after the entire installation has been completed.
2. Please confirm the following points before the test operation.
• The indoor unit and outdoor unit are installed properly.
• Tubing and wiring are correctly completed.
• The refrigerant pipe system is leakage checked.
• The drainage is unimpeded.
• The ground wiring is connected correctly.
• The length of the tubing and the added stow capacity of the refrigerant have been recorded.
• The power voltage fits the rated voltage of the air conditioner.
• There is no obstacle at the outlet and inlet of the outdoor and indoor units.
• The gas-side and liquid-side stop valves are both opened.
• The air conditioner is pre-heated by turning on the power .
3. According to the user’s requirement, install the remote controller frame where the remote controller’s
signal can reach the indoor unit smoothly.
4. Test operation
• Set the air conditioner under the mode of “COOLING” with the remote controller, and check the
following points per the “Owner’s manual “. If there is any malfunction, please resolve it as per
chapter “Troubles and Cause” in the “Owner’s Manual”.
1) The indoor unit
a. Whether the switch on the remote controller works well.
b. Whether the buttons on the remote controller works well.
c. Whether the air flow louver moves normally.
d. Whether the room temperature is adjusted well.
e. Whether the indicator lights normally.
f. Whether the temporary buttons works well.
g. Whether the drainage is normal.
h. Whether there is vibration or abnormal noise during operation.
i. Whether the air conditioner heats well in the case of the HEATING /COOLING type.
2) The outdoor unit
a. Whether there is vibration or abnormal noise during operation.
b. Whether the generated wind, noise, or condensed of by the air conditioner have influenced
your neighborhood.
c. Whether any of the refrigerant is leaked.
CAUTION
A protection feature prevents the air conditioner from being activated fro approximately 3 minutes when
it is restarted immediately after shut off.
SZ000289/En
06/23/2004, 2:39 PM
32
Summary of Contents for KN 24 RC
Page 50: ...9 2 REFRIGERATION DIAGRAMS Revision Y06 02 Service Manual KN Series 9 1 2 KN 30 R410A...
Page 51: ...9 3 REFRIGERATION DIAGRAMS Revision Y06 02 Service Manual KN Series 9 1 3 KN 36 R410A...
Page 52: ...9 4 REFRIGERATION DIAGRAMS Revision Y06 02 Service Manual KN Series 9 1 4 KN 36T R410A...
Page 53: ...9 5 REFRIGERATION DIAGRAMS Revision Y06 02 Service Manual KN Series 9 1 5 KN 45T R410A...
Page 57: ...11 2 CONTROL SYSTEM Revision Y06 02 Service Manual KN Series 11 1 3 Main PCB Controller...