9-2
9.1.2 Input type thermocouple “B”
1) Range 0 to +1820 °C
N.B.
••
The Thermocouple is not linearized. The Span value in °C is an average value.
••
The input terminals are as for mV input:
1+ and 8- for channel 1
2+ and 6- for channel 2
Note
: for all the informations regarding the configurations of the input, output and burn-out options of this
product, please refer to the procedures and tables described at page 5-19 chapter 5.9.
Span Calibration (Min
≅≅
270°C, Max=1820°C)
mV ( °C )
SW2-1
SW2-2
SW2-3
SW2-4
2.6 (
≅≅
270°C )
OFF
ON
OFF
OFF
3.6 (
≅≅
380°C )
OFF
ON
ON
ON
5.0 (
≅≅
550°C )
OFF
ON
ON
OFF
7.0 (
≅≅
770°C )
OFF
OFF
OFF
ON
10.0 (
≅≅
1110°C )
OFF
OFF
OFF
OFF
13.6 (
≅≅
1800°C )
OFF
OFF
ON
ON
Zero Calibration (Max=1600°C
)
°C
SW2-5
SW2-6
SW2-7
SW2-8
0
OFF
ON
OFF
OFF
500
ON
ON
OFF
OFF
750
OFF
OFF
OFF
OFF
920
ON
OFF
OFF
OFF
1090
OFF
ON
ON
OFF
1250
ON
ON
ON
OFF
1370
OFF
OFF
ON
OFF
1500
ON
OFF
ON
OFF
1600
OFF
ON
OFF
ON
Summary of Contents for HiD 2000 Series
Page 30: ......
Page 82: ......
Page 110: ......
Page 112: ...8 2 T temperature 1 2 Temperature 2 7 2 8 2 9 2 10 2 11 2 12 2 13 2 14 2 15 2 16 3 1...