10-2
10.1.2 Input type Potentiometer
Fixed Setting:
SW2
SW2-1
SW2-2
OFF
OFF
SW3
SW3-5
SW3-6
SW3-7
SW3-8
OFF
OFF
OFF
OFF
Input Setting:
Potentiometer (RP)
Ω
Ω
SW3-1
SW3-2
SW3-3
SW3-4
100
OFF
ON
ON
OFF
200
OFF
OFF
ON
ON
300
OFF
OFF
ON
OFF
When use potentiometer with more than 300
Ω
value a shunt resistor must be mounted in parallel to the
potentiometer on the terminal block. The parallel value must be equal to 100, 200 or 300
Ω
as the table above.
Shunt
sistor
PV Rp
PV
Rp
_Re
=
⋅
−
PV = Potentiometer value ( > 300
Ω
).
Rp = Parallel resistor
Output behaviour for wires interruption:
Begin of scale: Wire on pin 7 interrupted
End of scale:
Wire on pin 4 interrupted
Undefined:
Wire on pin 1 interrupted
Note
: for all the informations regarding the configurations of the input, output and burn-out options of this
product, please refer to the procedures and tables described at page 5-22 chapter 5.10.