5-22
Configuration options
The inputs can be configured as:
•
RTD ( 2, 3 or 4 wire ) or POT
•
Input Zero and Span Value
•
Burnout segnalation UP or DOWN (only for RTD 2, 3
wire)
The outputs can be configured as:
•
Current output 4-20 mA
•
Voltage output 1-5 V
The configuration is performed in the following way:
•
remove the module from termination board pulling-up
the tab on each side of the module
•
set the dip-switches according to the figure and to the
tables
The prongs for this model are trimmed to polarise it
according to it’s safety parameter. Please do not change.
See chapter 4.5 for more details.
Input
SW1-1 SW1-2 SW1-3 SW2-3
RTD 2 W
ON
ON
ON
ON
RTD 3 W
ON
ON
ON
ON
RTD 4 W
ON
OFF
OFF
ON
POT
OFF
OFF
OFF
OFF
Burnout
SW2-1 SW2-2
UP
ON
OFF
DOWN
OFF
ON
POT Input
OFF
OFF
Output
Ch.1
Ch.2
(Only for HiD 2072)
SW4-1
SW4-2
SW4-3
SW4-4
4-20 mA
OFF
OFF
OFF
OFF
1-5 V
ON
ON
ON
ON
Note: for input range setting refer to appendix
B for Zero and Span Tables. Also refer to
appendix B for calibrating instructions.