6-12
Input closed / relay output energised configuration:
a)
for HiD 2822, set the configuration switches as:
S1=OFF, S2=ON, S3=OFF, S4=ON
for HiD 2824, set the configuration switches as:
S1=OFF, S2=ON, S3=OFF, S4=ON, S5=OFF, S6=ON
,
S7=OFF, S8=ON
;
b)
connect the power supply at the termination board supply terminals; connect the resistor box Rc at the input
terminals; connect the first multimeter R1 (resistance mode) at the output terminal; connect the second multimeter
R2 (resistance mode) at the second output terminal only for model HiD 2822; set the supply at 24 V and switch it
on; the green power LED must go on;
c)
set the resistor box to 1 K
Ω
; the yellow status LED must be on and the red fault LED must be off; both
multimeters (HiD 2822) or the tested channel multimeter (HiD 2824) must give a "short circuit" reading;
d)
set the resistor box to 10 K
Ω
; both the yellow status and the red fault LED must be off; both multimeters (HiD
2822) or the tested channel multimeter (HiD 2824) must give an "open circuit" reading;
e)
set the resistor box to 0
Ω
(input short-circuit); the yellow status LED must be off and the red fault LED must be
on; both multimeters (HiD 2822) or the tested channel multimeter (HiD 2824) must give an "open circuit" reading;
f)
disconnect the resistor box (input open-circuit); the yellow status LED must be off and the red fault LED must be
on; both multimeters (HiD 2822) or the tested channel multimeter (HiD 2824) must give an "open circuit" reading;