9-6
9.1.6 Input type thermocouple “N”
1) Range 0 to +685 °C
2) Range 0 to +1300 °C
N.B.
The Thermocouple is not linearized. The Span value in °C is an average value.
Note
: for all the informations regarding the configurations of the input, output and burn-out options of this
product, please refer to the procedures and tables described at page 5-19 chapter 5.9.
Span Calibration (Min
≅≅
95°C, Max = 660°C)
mV ( °C )
SW2-1
SW2-2
SW2-3
SW2-4
2.6 (
≅≅
95°C )
OFF
ON
OFF
OFF
3.6 (
≅≅
130°C )
OFF
ON
ON
ON
5.0 (
≅≅
170°C )
OFF
ON
ON
OFF
7.0 (
≅≅
235°C )
OFF
OFF
OFF
ON
10.0 (
≅≅
320°C )
OFF
OFF
OFF
OFF
13.6 (
≅≅
445°C )
OFF
OFF
ON
ON
19.4 (
≅≅
570°C )
OFF
OFF
ON
OFF
Zero Calibration (Max=585°C
)
°C
SW2-5
SW2-6
SW2-7
SW2-8
+8
OFF
OFF
OFF
OFF
+63
ON
OFF
OFF
OFF
+110
OFF
ON
ON
OFF
+155
ON
ON
ON
OFF
+200
OFF
OFF
ON
OFF
+245
ON
OFF
ON
OFF
+290
OFF
ON
OFF
ON
+330
ON
ON
OFF
ON
+370
OFF
OFF
OFF
ON
+410
ON
OFF
OFF
ON
+450
OFF
ON
ON
ON
+490
ON
ON
ON
ON
+530
OFF
OFF
ON
ON
+565
ON
OFF
ON
ON
Span Calibration (Min
≅≅
260°C, Max = 1300°C)
mV ( °C )
SW2-1
SW2-2
SW2-3
SW2-4
9 (
≅≅
290°C )
ON
ON
OFF
ON
12 (
≅≅
375°C )
ON
ON
OFF
OFF
17 (
≅≅
505°C )
ON
ON
ON
ON
23 (
≅≅
660°C )
ON
ON
ON
OFF
33 (
≅≅
915°C )
ON
OFF
OFF
ON
47 (
≅≅
1285°C )
ON
OFF
OFF
OFF
Zero Calibration (Max=1090°C)
°C
SW2-5
SW2-6
SW2-7
SW2-8
0
OFF
OFF
OFF
OFF
+235
ON
OFF
OFF
OFF
+430
OFF
ON
ON
OFF
+610
ON
ON
ON
OFF
+765
OFF
OFF
ON
OFF
+940
ON
OFF
ON
OFF
+1090
OFF
ON
OFF
ON