PRODUCT MAINTENANCE
09/2020
41
NP-DK50 2x4VR 110-AD-A-1_09-2020
18.2. Check of product operation
Check aggregate condition
– the aggregates should be operating normally without excessive
vibration or noise. Troubleshoot any problem or call in service personnel if trouble is detected.
Visually inspect fan operation
– the fans must be operating when the aggregates are running.
Troubleshoot any problem or call in service personnel if trouble is detected.
Check to ensure the power cord, the connecting compressed air hoses are undamaged. Replace
damaged components or call in service personnel.
Check the ambient temperature
– the ambient temperature must be below the temperature limit
(40°C). Cool the space if the temperature is high.
Compressor with air dryer - open the plug on the condensate collecting vessel and drain the
condensate.
Check the service indicator on the display screen and schedule service as needed.
Check the operating condition of the equipment (see Chapter 18.4).
18.3. Check the compressed air connections for leaks and inspect the equipment
Leak testing
Check the compressor's compressed air lines for leaks during operation
– pressure supplied by
the compressor.
Use a leak analyser or soapy water to check all joints and connections for leaks. Tighten or reseal
the connection where leaks are found.
Inspecting the equipment
Check the condition of the compressor aggregate for normal operation and noise levels.
Fan operation check
– the fans must be running during the defined compressor work cycles.
Check function of the temperature switch (B2)
– heat the temperature switch to temperature
above 40°C (e.g. using a heat gun – Be careful, do not operate with high temperature on plastic
components in the surrounding, it can cause deformation of plastic materials). Fan E1, E3 - the
compressor must be under voltage.
Check filters condition
– filters must be undamaged and sufficiently clean.
Check condition of the pump itself, check if there is no dirt inside the crankcase or clearance in
the crankshaft.
Replace any defective parts if there are any failures.
Replace any defective parts as needed.
Check the solenoid valves in the valve module
– the valves should cyclically cycle between the
chambers based on the description of the operation.
Check the operating condition of the equipment (see Chapter 18.4).
18.4. Inspection of electrical connections
Risk of electric shock.
Inspect the product’s electrical connections when the mains are disconnected.
Check mechanical function of the main switch.
Check if the power cable and conductors are not damaged.
Summary of Contents for DK50 2x4VR/110/M
Page 1: ...DK50 2x4VR 110 User manual Benutzerhandbuch N vod na pou itie...
Page 2: ......
Page 4: ...CONTENTS 4 INHALT 57 OBSAH 111...
Page 14: ...PRODUCT DESCRIPTION NP DK50 2x4VR 110 AD A 1_09 2020 14 09 2020 Fig 2 Adsorption dryer...
Page 15: ...PRODUCT DESCRIPTION 09 2020 15 NP DK50 2x4VR 110 AD A 1_09 2020 Fig 3 Cabinet...
Page 66: ...PRODUKTBESCHREIBUNG NP DK50 2x4VR 110 AD A 1_09 2020 66 09 2020 Abb 2 Adsorptionstrockner...
Page 67: ...PRODUKTBESCHREIBUNG 09 2020 67 NP DK50 2x4VR 110 AD A 1_09 2020 Abb 3 Geh use...
Page 120: ...POPIS V ROBKU NP DK50 2x4VR 110 AD A 1_09 2020 120 09 2020 Obr 2 Adsorp n su i...
Page 121: ...POPIS V ROBKU 09 2020 121 NP DK50 2x4VR 110 AD A 1_09 2020 Obr 3 Skrinka...
Page 166: ......
Page 167: ......