WARNING
9.2
Connecting the battery
Risk of injury!
Do not place anything between the inverter terminal and the ring cable lug.
Otherwise, this can lead to overheating.
Do not apply an antioxident to the terminals before the terminals are securely
connected.
Before establishing the final DC connection or closing the DC power switch/
circuit breaker, ensure that plus (+) is connected to plus (+) and minus (-) is
connected to minus (-).
For safe operation and the observance of regulations, it is necessary, to install a
separate DC overcurrent protection or an isolating device between the battery and
the inverter. In many applications, an isolating device may not be necessary.
Nevertheless, the installation of an overcurrent protection is still required. Please
refer to the typical current in the following table for the required fuse size or the
contact breaker size.
All the wiring must be carried out by qualified personnel.
For system safety and efficient operation, it is very important to
only use the recommended cable and connector sizes for the
battery connection.
Ring cable lug:
Model
Typical
current
Battery
capacity
Cable size
Ring cable lug
Tighten-
ing torque
cable
mm
2
Measurements
D (mm)
L (mm)
3KW
200A
200Ah
1*70mm²
70
6.4
49.7
2~3 Nm
2*25mm²
25
6.4
49.7
5KW
200A
200Ah
1*70mm²
70
6.4
49.7
2~3 Nm
2*25mm²
25
6.4
49.7