Innovating power.
Control and display elements - Page 33
Solar inverter | V1.7
the loads with power at
the same time.
The mains power supply
only supplies the loads
with power if the battery
voltage either drops to
the low warning voltage
or the setting point in
program 12 or solar and
battery power are not
sufficient.
02
Total charging
power for solar and
mains charging
devices.
(Total charging power
= mains charging
power + PV solar
charging power)
60A (preset)
The setting range of the
3KW model extends from
10 A to 120 A. Setting in
10 A steps.
The setting range of the
5-kW model extends
from 10 A to 140 A.
Setting in 10 A steps.
05
Selection of the
accumulator
types
Absorbent Glass Mat (AGM)
(preset)
Lead acid battery (FLD)
When "user defined" is
selected, the battery
charging voltage and the
low DC cut-off voltage
can be inserted in the
programs 26, 27 and 29.
Pylontech
(Manufacturer's name)
When selected, the
programs 02, 26, 27 and
29 are automatically
arranged. No additional
settings are necessary.