Connection - Page 65
Solar inverter | V1.7
Damage to devices without time delay function!
Air conditioners require at least 2-3 minutes to restart as sufficient time is
required for offsetting the refrigerant gas in the cycle. If a power failure occurs
and recovers after a brief period, this can lead to damages to your connected
devices.
To prevent this type of damage, please check with the air conditioner
manufacturer prior to installation if the device is equipped with a time delay
function. Otherwise, this inverter/charging device triggers an overload fault and
interrupts the output to protect your device, but this still sometimes causes
internal damage to the air conditioner.
CAUTION
Damage to devices due to incorrectly connected polarity!
Make sure to connect the AC cable with the correct polarity. If the L and N cables
are incorrectly connected, this can lead to a short circuit of the power supply if the
inverter is operating in parallel.
CAUTION
Damage to the generator due to inappropriate generator power!
The recommended generator power should be at least twice the
inverter power.
Generator output: pure sine wave
Effective value range of the output voltage of the generator: 180 ~
270VAC
Frequency range of the generator output: 45 Hz ~ 63 Hz
CAUTION