UPS MTD-XL
Introduction
MTD series
14
1.8
Positioning
Do not install in an area in which combustible vapours arise e.g. from
petrol tanks, engine compartments, etc.
The UPS is designed for operation in ventilated rooms with an ambient tem-
perature of 0° to 40°C.
If the UPS is exposed to severe and quick temperature changes, there is dan-
ger of condensation. Before you take additional steps, an acclimatization pe-
riod of at least 2 hours is to be observed.
Never place or operate the device in a moist environment. Keep liquids away
from the device.
The UPS may not be placed in the vicinity of heat sources.
The horizontal positioning is to be observed.
Ensure that the back side and the front side of the device are at least 10 cm
from other objects for ventilation in order to prevent trapped air and too much
warming. Make sure that the air openings cannot be covered, e. .g. through
sucked-in paper, material, etc.