UPS MTD-XL
UPS
Installation and Connection
MTD series
57
6.3
Connection sequence
Connect the accumulator module with the UPS.
Connect the UPS with the mains power supply; both, the mains and the
UPS must be safely switched-off during this process.
Before the appliances are connected to the outlet, the basic configuration
must be completed.
Connect the appliance/s with the UPS. Make sure that all appliances are
switched-off.
6.3.1
Configuration of the remote shut-down
Conductor
function
Size of connecting wire
Recommended wire
size
EPO
4
– 0.32 mm
2
(12 - 22 AWG )
0.82 mm
2
(18 AWG)
Leave the EPO-plug installed on the EPO-port of the UPS even if the EPO-
function is not needed.
Fig. 6-3-1
EPO-plug
Please see the information regarding the connection of the EPO-contact in
chapter 3.2.5 EPO-port.
If the contact is closed, the output is active.
If the contact is open, the output is turned off.
Summary of Contents for ACX11MST1K0000XL
Page 7: ...UPS MTD XL Introduction MTD series 7...
Page 31: ...UPS MTD XL UPS Device Description MTD series 31 Fig 3 2 3 Relay slot card...
Page 32: ...UPS MTD XL UPS Device Description MTD series 32 Fig 3 2 4 Relay card diagram...
Page 41: ...UPS MTD XL UPS Device Description MTD series 41...
Page 77: ...UPS MTD XL MTD series 77 EFFEKTA Regeltechnik GmbH Rheinwaldstra e 34 D 78628 Rottweil...