UPS Adira (6kVA, 6kVA XL, 10kVA,
10kVA XL 1-phase)
Operation
Adira series
66
Parameters
Settings
Default value
User password
<enable><disable>
If this value is set to <
enable
>, you have to
enter the password.
disable
Audio alarm
<enable><disable>
If this value is set to <
disable
>, the UPS is
silent and no alarm signals will sound.
enable
Output voltage
<208><220><230><240>
230V
Output frequency
<50HZ><60HZ>
< Autosensing>
On <
autosensing
> the output frequency is
identical to the input frequency.
autosensing
Power strategy
<normal>
<high efficiency>
<converter>
Normal
DC start
<enable><disable>
cold boot
enable
Site wiring alarm
<enable><disable>
If this value is set to <
enable
>, a warning
message appears in the display, when the
protective earth conductor is not connected or
if phase and neutral have been swapped.
enabled
Ambient temperature
warning
<enable><disable>
If this value is set to <enable>, a warning
message appears in the display when the
ambient temperature reaches 45°C.
enabled
Automatic battery tests
period
<0>….<31days>
If this value is "0", the automatic battery test is
turned off.
7 days
Auto restart
<enable><disable>
<
enable
> means that the UPS performs an
automatic restart in normal operating mode, if
it was shut down due to a low battery charge
status.
enable
Automatic overload
restart
<enable><disable>
<
enable
> signifies that the UPS switches from
bypass to line mode after the batteries have
been charged to 70 %.
enable
Auto bypass
<enable><disable>
disable