UPS Adira (6kVA, 6kVA XL, 10kVA,
10kVA XL 1-phase)
Operation
Adira series
61
Menu
Parameters
Settings
Factory set-
ting
Buzzer mute
Buzzer mute
<No><Yes>
No
:
The keypad tones of the UPS are
turned on.
Yes
:
The keypad tones of the UPS are
turned off.
No
Single UPS
battery test
Status battery test
The status of the latest battery tests
is displayed here.
Start battery test
<No><Yes>
No
:
No battery test is performed.
Yes
:
A battery test is performed.
You can configure the cycle for a
battery test in the menu "automatic
battery test period".
chapter 7.3.6 Settings Menu
No
Clear EPO
status
Status
Displays the EPO-status.
Clear
<No><Yes>
No
:
If the EPO had been triggered, it will
not
be reset.
Yes
:
If the EPO had been triggered, it will
be reset.
No
Reset fault
status
Status
Displays whether the fault mode is
active or inactive.
Reset fault
<No><Yes>
No
:
If a fault is pending on the UPS, it
will
not
be reset.
Yes
:
If a fault is pending on the UPS, it
will be reset.
No
Clear event log
Total events
Displays the number of messages.