UPS Adira (6kVA, 6kVA XL, 10kVA,
10kVA XL 1-phase)
Safety Instructions
Adira series
17
2.6
Operation
Before the appliances are connected to the outlet, the basic configuration must
be completed. Especially the output voltage is of high importance regarding the
appliances.
The UPS-system contains an energy storage (accumulators). This means that
the outlet can be current-carrying even when the UPS is not connected to the
mains input terminal.
To completely shut-down the UPS, first disconnect the mains connection and
then hold the "OFF" button pressed for more than 3 seconds. Wait for the UPS
to turn off, before disconnecting the power connection (feeder cable between
the UPS and the appliance). Ensure that no liquids or foreign matter enter the
UPS. Avoid a constant load of more than 80% on the output to protect the UPS.
The displayed output load should only be taken as a reference point, separate
measuring is necessary to determine the exact output load.
2.7
Working with Accumulators
Attention
– Danger of electric shocks and burns.
Accumulators can cause electric shocks and have a high short-circuit cur-
rent, which can cause burns.
Unauthorized persons should not have access to the accumulators.
Do not place accumulators in the vicinity of heat sources and do not throw
them into a fire. Explosion hazard!
Do not open or destroy accumulators. The released electrolyte presents a
great danger to health and the environment (chemical burns to skin and
eyes, toxic).