UPS Adira (6kVA, 6kVA XL, 10kVA,
10kVA XL 1-phase)
Operation
Adira series
67
<
enable
> signifies that the UPS switches to
bypass mode after start up.
<
disable
> signifies that the UPS does not start
in bypass mode, but switches to bypass mode
if a fault is detected or the batteries are over-
loaded.
Short circuit clearance
<enable><disable>
<
enable
> means the UPS stays in line mode
and no warning message is displayed if a short
circuit at the output last less than four sec-
onds.
<
disable
> means that the UPS switches to
fault mode and displays a warning signal if a
short circuit at the output lasts more than four
seconds.
disable
Bypass voltage low limit
<167V>….<215V>
176V
Bypass frequency high
limit
<+1%(50.5HZ)>….<+10%(55.0HZ)>
10%
Bypass voltage high limit
<245V>….<276V>
264V
Bypass frequency low
limit
<-
10%(45.0HZ)>….<-1%(49.5HZ)>
10%
HE voltage low limit
<-
10%(207.0V)>….<-0,5%(218.5V)
5%
HE voltage high limit
<+5%(241.5V)>….<+10%(253.0V)>
5%
HE frequency low limit
<-
10%(45.0HZ)>….<-1%(49.5HZ)>
5%
HE frequency high limit
<+1%(50.5HZ)>….<+10%(55.0HZ)>
5%
Battery quantity
<19>….<21>
Displays the number of internal, integrated
accumulators.
20
External battery module
<0>….<9>
The selected value gives the number of exter-
nal battery modules.
0
Set running time
Day:0000-9999
Hour:00-23
Minute:00-59
Second:00-59
Running Time
LCD contrast
<-
5>….<+5>
The contrast of the LCD-Display can be ad-
justed here between
– 5 and + 5.
0