UPS Adira (6kVA, 6kVA XL, 10kVA,
10kVA XL 1-phase)
Introduction
Adira series
13
1.8
Positioning
Do not install in an area in which combustible vapours arise e.g. from pet-
rol tanks, engine compartments, etc.
The UPS is designed for operation in ventilated rooms with an ambient tempera-
ture of 0° to 40°C.
If the UPS is exposed to severe and quick temperature changes, there is danger
of condensation. Before you take additional steps, an acclimatization period of
at least 2 hours is to be observed.
Never place or operate the device in a moist environment. Keep liquids away
from the device.
The UPS may not be placed in the vicinity of heat sources.
The UPS may only be set-up in a vertical position and on castors.
Ensure that the back side and the front side of the device are at least 10 cm
from other objects for ventilation in order to prevent trapped air and too much
warming. Make sure that the air openings cannot be covered, e.g. through
sucked-in paper, material, etc.