20
E D G E I Q H A N D B O O K
7.
A P P E N D I X A : P R O D U C T I N F O R M A T I O N
Product Name
: EdgeIQ
Product model number
: EE-202-0050 Series
Configuration
: 5KVA, Single Phase, 240 VAC
Serial number
: EE-202-0050-005-0000001 to EE-202-0050-005-999999
Input Voltage
180 – 275VAC, 100A max.
Output (Bypass Mode)
V
out
= V
in,
I
out
= I
in
Output (Regulating Mode)
210 – 254VAC Nominal 220VAC, 22.7A max.
(Vout is remotely Network programmable)
VA Rating
5 kVA regulation mode,63A bypass mode
Frequency
50 Hz
Operating temperature range
-10 to 45 °C Ambient
Ingression Grade
IP 54
Max. Humidity
95% (Non-Condensing)
Dimensions
H 539 X W 263 X D 92 mm Metal Enclosure
Recommended breaker rating
Switchboard Circuit Breaker 63A / 80A
The wiring installation must meet Australia and
New Zealand Standards below:
• AS/NZS 3000 (Electrical Installation- Wiring Rules) and
• AS/NZS 3008 (Electrical Installations – Selection of Cables)
Unit weight
10 kg
Patents
Patents pending
Table 1: Wiring installation
TERMINAL
WIRING INSTALLATION
CONNECTIONS
TYPE
TORQUE
(N m)
Standard
install
: 40/63A
Non-Standard
install
:
80/100A
Switchboard Circuit
Breaker
Live, Neutral and Earth
Wiring for
Standard install,
for
switchboard main breaker 40/63A, see
wiring diagram section 4.1 and 4.2 on
page 13 and 14
.
Note: For a
Non-Standard install
, for
switchboard main breaker of 80/100A,
appropriate wire sizing should be
installed in accordance to AS/NZS 3000
and AS/NZS 3008
.
Wiring installation must meet Australia
and New Zealand Standards:
AS/NZS 3000 (Electrical Installation-
Wiring Rules)
and
AS/NZS 3008 (Electrical Installations –
Selection of Cables)
Terminal Block
3 Wires
1.2
Current Transformer
333mV @ 50A, 600V
2 Poles, 3.5 mm
Plug in Connector
N.A.
Summary of Contents for EDGEIQ EE-202-0050