The screen contains the following parameters:
Interface - CAN2
Input
Default
Setting of the operating mode for the 2nd CAN bus interface
CI 4500:
no function or as CAN bus repeater for details, see
CAN bus - Connection of E*LDS Components
--,
Repeater
---
Interface COM1/Modem - all CI 4x00
The COM1 interface is configured in this screen. The COM1 interface can be used as modem or as
COM port server. When the interface is used as COM port server, the serial interface of the GLT 3010 can be
accessed via the Ethernet connection of the CI 4x00.
Use of the interface as modem
Interface - COM1/Modem
Input
Default
Telephone number
Telephone number of the modem at the system
centre (connected to COM1)
max. 19 characters
-
Dialling prefix
Number for the outside line
max. 8 digits
-
MSN
19-digit terminal device identification number
- for direct outside line, this is the telephone
number (without the dialling prefix))
- in the normal case (i.e. for extensions), this is
the direct dial number
max. 19 characters
0
PIN
PIN
-
Alarm if modem not available
Should an alarm be signalled if the modem is
not detected?
If the check mark is set and no modem is
detected at the interface,
the alarm "Modem Fault" is output after 2
minutes.
Y/N
Y
Use of the interface as COM port server
Interface - COM1 / COM port
server
Input
Default
TCP port
Input of the TCP/IP port of the COM
port server
Numbers (1 ...65535)
1041
Baud rate
Baud rate of the serial connection to the
GLT3010
300, 1200, 2400, 4800, 9600, 19200,
38400, 57600, 115200
38400
Interface COM2 - all CI 4x00
This screen is used for the M-bus.
No configuration is currently envisaged.
For detailed information, see chapter Modem.