Firmware V6.6.9
29.07.2020
97/147
Special inputs
Shunt lock
Predefined designation of the special input (digital input)
Priority XX
Priority of the signal / alarm input
Delay time [sec.] XX
Delay time of the signal / alarm in seconds
Quiescent current (low-active) X
Alarm is signalled if
- quiescent current = Yes: (signal voltage not present low-active)
- quiescent current = No: (signal voltage is present high-active)
Input X
Connection of the input
1)
Status XX
Current status of the input: OK = light grey, no signalling Waiting = yellow:
signalling, delay time running, Message = green: no alarm Alarm = red: signalling,
alarm / message has been tripped
1)
Designations of the supported modules / inputs:
CI 4x00
system centre, internal inputs IN1 / IN2 (terminals A1, A2 / B1, B2)
SIOX1 1. extension module, inputs 1 .. 12
SIOX2 2. extension module, inputs 1 .. 12
SIOX3 3. extension module, inputs 1 .. 12
SIOX4 4. extension module, inputs 1 .. 12
DDC1 1. GLT DDC module 1
DDC2 2. GLT DDC module 2
DDC3 3. GLT DDC module 3
DDC4 4. GLT DDC module 4
Note: GLT = building control and DDC = Digital Direct Control
9 Menu 2-9 - General Information
The screen for general information of the store is called using this button.
The screen contains the following parameters:
General information
Read only!
Operating time of the system centre
Years / days /hours
Operating time of the display
Years / days /hours
System up time
Years / days / hours / minutes / seconds
The digital special inputs are configured using Menu 4-1-3. Detailed description of the functions can be
found in chapters