Firmware V6.6.9
29.07.2020
96/147
•
•
•
•
•
The screen contains the following parameters:
Signal inputs
Message text
Message text of the signal input (digital input)
Priority XX
Priority of the signal / alarm input
Delay time [Min.] XX
Delay time of the signal / alarm in minutes
Quiescent current (low-active) X
Alarm is signalled if
- quiescent current = Yes: (signal voltage not present, low-active)
- quiescent current = No: (signal voltage is present, high-active)
Input X
Connection of the input
1)
Status XX
Current status of the input:
OK = light grey: no signalling
Wait = yellow: signalling, delay time running,
message = green: no alarm
alarm = red: signalling, alarm / message has been tripped
1)
Designations of the supported modules / inputs:
CI 4x00 system centre, internal inputs IN1 / IN2 (terminals A1, A2 / B1, B2)
SIOX1 1st extension module, inputs 1 .. 12
SIOX2 2nd extension module, inputs 1 .. 12
SIOX3 3rd extension module, inputs 1 .. 12
SIOX4 4th extension module, inputs 1 .. 12
DDC1 1st GLT DDC module 1
DDC2 2nd GLT DDC module 2
DDC3 3rd GLT DDC module 3
DDC4 4th GLT DDC module 4
Note: GLT = Building Control System and DDC = Digital Direct Control
8 Menu 2-8 - Special Inputs
The digital special inputs of the system centre are called up using this button. All important
parameters and the status of the inputs are displayed there.
following special inputs are available:
shunt lock
emergency power supply
sprinkler alarm
store lighting
setpoint toggle
The screen contains the following parameters:
The digital signal and alarm inputs are configured using Menu 4-1-2. Further information about the
functions is contained in the chapter
.
As the display for all special inputs is identical, the explanations are provided using the example of the
“shunt lock”.