Firmware V6.6.9
29.07.2020
103/147
•
•
•
•
•
Menu 4-1-3 - Special Inputs
The special inputs of the system centre are called up using this button. See chapter
for details. All important parameters and the status of the inputs are displayed there. The required special inputs
can be selected and configured using the corresponding screen. Special inputs are permanently predefined in
the system centre and cannot be deleted or added; it is only possible to delete their configuration.
The following special inputs are available:
shunt lock,
emergency power supply
sprinkler alarm
store lighting
setpoint toggle
The screen contains the following parameters:
Special inputs
Eingabe
Vorgabe
Message text
Shunt lock (predefined designation of the
special input)
-
Shunt lock
PriorityXX
Priority of the signal / alarm input
--, 0..99
0
Delay [sec.] XX
Delay time of the signal / alarm in seconds
0..255
1
Quiescent current (low-active) X
Alarm is signalled if
- quiescent current = Yes: (signal voltage not
present, low-active)
- quiescent current = No: (signal voltage is
present, high-active)
Y/N
N
Signal input
Module
Module
1)
to which the message / alarm signal
is connected
SIOX1 ..SIOX4
-
Submodule XX
Submodule
1)
to which the message / alarm
signal is applied; this is ONLY visible if
module=DDC1..DDC4 has been selected
1..4
-
Input XX
Input
1)
to which the message / alarm signal is
applied
1..12
-
Status XX
Current status of the input:
OK = light grey, no signalling
Waiting = yellow: signalling, delay time running,
Message = green: no alarm
Alarm = red: signalling, alarm / message has
been tripped
-
-
1)
Designations of the supported modules / inputs:
CI 4x00
system centre, internal inputs IN1 / IN2 (terminals A1, A2 / B1, B2)
SIOX1 1. extension module, inputs 1 .. 12
SIOX2 2. extension module, inputs 1 .. 12
As the configuration for all special inputs is identical, the explanations are provided using the example
of the “shunt lock”.