Table 4.9
100-240VAC, L-to-E, Transformer-Isolated Coupling Circuit Component Values
Comp
Value
Specifications
Vendor / Part Number
C1 0.033µF ±10%,
≥
250VAC, X2 type
(1)
Nissei Denki / Arcotronics
R40333K275XXXX
C2 0.82µF ±5%,
≥
50VDC, metalized polyester
Matsushita Electric / ECQ-V1H824JL
C3
≥
120µF
±20%, 16VDC, aluminum electrolytic,
≤
0.3
Ω
ESR @100kHz
Matsushita Electric / ECA-1CFQ121
C4 0.033µF ±5%,
≥
50VDC
AVX / SR205C333JAA
D1 1A
Reverse
breakdown
≥
50V, surge current
≥
30A for
8.3mS, reverse recovery
≤
200nS
1N4935
F1
6A
250VAC, slow blow
(2)
L2 27µH ±10%,
Imax
≥
500mA, RDC
≤
0.3
Ω
TAIYO YUDEN / LAL05TB270K
L3, L4
1.0mH
±10%, Imax
≥
30mA, RDC
≤
50
Ω
TAIYO YUDEN / LAL03NA102K
R1
1M
Ω
±5%, 1/4W, max working volt
≥
360VDC
(4)
R2
82
Ω
-L4RDC
(3)
±5%,
≥
1/16W
T1
See Appendix A
PROTECT none
240VAC
240VAC
For indoor branch circuits no component required
For power entry use AC gas discharge tube
(5)
For outdoor use AC gas discharge tube
(5)
n/a
CPClare / AC240L
CPClare / AC240L
Table 4.10
100-120VAC, L-to-E, Transformer-Isolated Coupling Circuit Component Values
Comp
Value
Specifications
Vendor / Part Number
C1 0.068µF ±10%,
≥
250VAC, X2 type
(1)
Nissei Denki / Arcotronics
R40683K275XXXX
C2 0.82µF ±5%,
≥
50VDC, metalized polyester
Matsushita Electric / ECQ-V1H824JL
C3
≥
120µF
±20%, 16VDC, aluminum electrolytic,
≤
0.3
Ω
ESR @100kHz
Matsushita Electric / ECA-1CFQ121
C4 0.068µF ±5%,
≥
50VDC
AVX / SR205C683JAA
D1 1A
Reverse
breakdown
≥
50V, surge current
≥
30A for
8.3mS, reverse recovery
≤
200nS
1N4935
F1
6A
125VAC, slow blow
(2)
L2 5.6µH ±10%,
Imax
≥
500mA, RDC
≤
0.4
Ω
TAIYO YUDEN / LAL04NA5R6K
L3, L4
1.0mH
±10%, Imax
≥
30mA, RDC
≤
50
Ω
TAIYO YUDEN / LAL03NA102K
R1
1M
Ω
±5%, 1/4W, max working volt
≥
200VDC
(4)
R2
82
Ω
-L4RDC
(3)
±5%,
≥
1/16W
T1
See Appendix A
PROTECT none
120VAC
120VAC
For indoor branch circuits no component required
For power entry use AC gas discharge tube
(5)
For outdoor use AC gas discharge tube
(5)
n/a
CPClare / AC120L
CPClare / AC120L
(1)
An X2-type capacitor is required for adequate surge immunity in branch circuit applications.
(2)
In some applications a fuse may not be required. Consult applicable safety standards.
(3)
The value of R2 should be selected so that the series combination the DC resistance of L4 and R2is equal to 82
Ω
.
(notes are continued on next page)
L
ON
W
ORKS
PLT-22 Transceiver User’s Guide
4-25
Summary of Contents for LONWORKS PLT-22
Page 6: ...iv Echelon...
Page 14: ...1 8 Introduction...
Page 67: ...LONWORKS PLT 22 Transceiver s User Guide 5 7 Figure 5 3 Capacitor Input Power Supply Schematic...
Page 92: ...6 10 Design and Test for Electromagnetic Compatibility...
Page 110: ...7 18 Communication Performance Verification...
Page 114: ...8 4 References...
Page 118: ...A 4 Appendix A...