PLT-22 Transceiver Coupling Circuit Components Key
Specifications
Item Check
When
Completed
Description
31
Fuse
F1
6Amp rating (DC resistance
≤
0.1
Ω
)
Time lag, i.e., slow blow type
Proper voltage rating
32
Capacitor
C1
Proper value selected
10% (or better) tolerance
Proper voltage rating (including AC or DC)
Safety listing, if applicable
33
Capacitor
C2
Metalized polyester (required for surge immunity)
Proper value selected
Proper tolerance
Proper voltage rating
34
Capacitor
C4
Value such that C4*L4=C1*L1
5% tolerance
≥
50VDC rating
35
Inductor L1,L3,L4
1.0mH value
DC current rating
≥
30mA
DC resistance
≤
50
Ω
10% (or better) tolerance
36
L1 and L3 spaced >1 cm (0.4") apart
37
Inductor
L2
Proper value selected per chapter 4
DC current rating
≥
500mA
DC resistance
≤
0.3
Ω
10% (or better) tolerance
38
Transformer
T1
PCI 0505-0671 or equivalent
EXCEL EXL-165 or equivalent
Transpower TTI7143 or equivalent
L
ON
W
ORKS
PLT-22 Transceiver User’s Guide
B-5
Summary of Contents for LONWORKS PLT-22
Page 6: ...iv Echelon...
Page 14: ...1 8 Introduction...
Page 67: ...LONWORKS PLT 22 Transceiver s User Guide 5 7 Figure 5 3 Capacitor Input Power Supply Schematic...
Page 92: ...6 10 Design and Test for Electromagnetic Compatibility...
Page 110: ...7 18 Communication Performance Verification...
Page 114: ...8 4 References...
Page 118: ...A 4 Appendix A...