87
Version 1.0 - 2012
Manual XrGi 20G-To
1: Manual stop
The operator has stopped automatic operation of the system, i.e. by pressing a key.
3: Manual stop while calibrating
The operator has stopped the system, i.e. by pressing a key, while it was being calibrated.
4: Storage full
The storage tank is full.
This is a normal, automatic stop. The system will restart once power and heat conditions require it do so.
5: Storage 2/3 full
Sensors 1 and 2 are hot, power consumption is low.
This is a normal, automatic stop. The system will restart once power and heat conditions require it do so.
6: Power consumption low
Sensor 1 is hot, power consumption is low. However, the system will not shut down for at least 20 min.
This is a normal, automatic stop. The system will restart once power and heat conditions require it do so.
7: No power output
The production meter in the IQ-Control Panel is not recording any power production.
This will cause an alarm stop.
This service code is displayed after just a few seconds to ensure no unburned gas is released into the exhaust.
Potential faults are:
Ignition problems
Gas mixing problems
The production meter in the IQ-Control Panel or connection to the IQ-Control Panel is faulty.
10: Oil pressure probe defective
The oil pressure is recorded while the engine is not running. This fault generates a system alarm stop immediately.
This fault is usually due to a defective oil pressure sensor, other reasons can be a broken cable or a short circuit.
12: No oil pressure
There is no oil pressure 15 seconds after starting.
This will cause an alarm stop.
There may be a number of causes here:
The engine is not running because a fuse has blown, for example.
There is no oil. If this is the case top up oil, but check why there was not enough oil in the first place.
Oil pressure sensor faulty.
18: Power output too high when calibrating
This service code appears when power production surges during calibration. This means that adjusting the stepper engine
even slightly causes power production to surge suddenly.
When this service code is posted, the system ventilates and calibration restarts. If this alarm service code occurs three times
within an hour, this will cause an alarm stop.
This code may be displayed due to problems with the stepping engine. However, it is more likely that the engine is not running
steadily, possibly due to an interruption shortly before.
6.2.1. service
Summary of Contents for XRGI 20G-TO
Page 1: ...System components Installation INSTRUCTIONS...
Page 2: ...2 Version 1 0 2012 Manual XRGI 20G TO...
Page 98: ...98 Version 1 0 2012 Manual XRGI 20G TO...
Page 131: ...131 Version 1 0 2012 Manual XRGI 20G TO...
Page 152: ...152 Version 1 0 2012 Manual XRGI 20G TO...
Page 153: ...153 Version 1 0 2012 Manual XRGI 20G TO...
Page 154: ...154 Version 1 0 2012 Manual XRGI 20G TO...
Page 155: ...155 Version 1 0 2012 Manual XRGI 20G TO...
Page 156: ...156 Version 1 0 2012 Manual XRGI 20G TO...
Page 157: ...157 Version 1 0 2012 Manual XRGI 20G TO...
Page 158: ...158 Version 1 0 2012 Manual XRGI 20G TO...
Page 159: ...159 Version 1 0 2012 Manual XRGI 20G TO...
Page 160: ...160 Version 1 0 2012 Manual XRGI 20G TO...
Page 161: ...161 Version 1 0 2012 Manual XRGI 20G TO...
Page 162: ...162 Version 1 0 2012 Manual XRGI 20G TO...
Page 166: ...166 Version 1 0 2012 Manual XRGI 20G TO Notes...
Page 167: ...167 Version 1 0 2012 Manual XRGI 20G TO...
Page 168: ......