SC200 Handbook
76
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
► To manually control a digital output
Either:
In DCTools/Web go to
Digital Outputs
:
Expand the
Digital Outputs
table.
In the
Control State
column of the required digital output, select
Active
or
Inactive
.
Or, use the SC200 keypad to go to
Digital Outputs
:
Select the required digital output. Press
Edit
.
Select
Active
or
Inactive
. Press
Save
.
The
DO Manual
alarm (if enabled) will activate.
The corresponding digital output will Energize or De-Energize, as selected in the
Active
State
column of the
Digital Outputs
table.
While
Active
or
Inactive is selected, t
he DO will not be operated by any active alarms mapped
to it. Set Control State back to Automatic to allow mapped alarms to operate the digital output.
► To set the state of a digital output from PowerManagerII
In
DCTools
, set the
Group
of one or more digital outputs to a non-zero value.
Only digital outputs with a non-zero Group are visible in PowerManagerII
In
PowerManagerII
select the SiteManager group item.
Click on the
Realtime
tab.
From the drop down list beside the digital output select
Active Manual
or
Inactive Manual
.
The
DO Manual
alarm (if enabled) will activate.
The corresponding digital output will Energize or De-Energize, according to its
Active State.
While
Active Manual
or
Inactive Manual is selected, t
he DO will not be operated by any active
alarms mapped to it. Set Control State back to Automatic to allow mapped alarms to operate the
digital output.
► To configure a digital output
1
In DCTools/Web go to
Digital Outputs
. Expand the
Digital Outputs
table.
2
Select a Digital Output (1-6*).
Other Digital Outputs will be available if additional I/O boards and/or SiteSure-3G modules
are connected. See details in the dc power system Installation and Operation Guide.
3
Configure the following parameters to suit the application.
To change a setting, double-click and select from drop down list or edit the text.