SC200 Handbook
34
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
Rectifier Comms Lost Alarm
When a rectifier is removed (or a fault interrupts rectifier communications), the SC200 will
display an alert message and sound an alert alarm (if
Audible Alarms
are enabled). After the
Alarm Recognition Period
, a
Rectifier Comms Lost
alarm will activate.
A Multiple Rectifier Comms Lost alarm will activate (after the
Alarm Recognition Period)
if
more than one rectifier is affected.
► To prevent a
Rectifier Comms Lost
alarm when a rectifier is removed
Press any key within the
Alarm Recognition Period
, to cancel the alert.
Rectifier Shutdown
Rectifier shutdown can be disabled, controlled manually, or controlled automatically based on
the total rectifier load current (see Load Based Rectifier Shutdown on page
► To disable Rectifier Shutdown
Use the SC200 keypad to go to: Rectifiers > Settings (tab) > set Rectifier Shutdown to
Disabled.
Or, in DCTools/Web go to: Rectifiers > Configuration> set Shutdown to Disabled.
Manual Rectifier Shutdown
► To shut down a rectifier
In DCTools/Web go to:
Rectifiers
>
Configuration
.
Set
Shutdown
to
Manual
.
In the
Rectifiers
table select the
Shutdown
check box (DCTools) or click Shutdown (Web).
The rectifier will shut down and the yellow LED will be on.
This function will normally only be used for testing purposes. When the testing is complete, set
Shutdown
back to its previous setting (
Disabled
or
Automatic
).
Rectifier Restart
► To restart all shutdown rectifiers
Use the SC200 keypad to go to: Rectifiers > Rect. Settings (tab) > Restart All Rectifiers.
Or, in DCTools/Web go to:
Rectifiers
. Click
Restart All.
► To restart individual rectifiers
In DCTools/Web go to:
Rectifiers
.
For each rectifier clear the
Shutdown
check box (DCTools) or click Startup (Web).
The rectifier(s) will then resume normal operation.
The SC200 will restart any shutdown rectifiers if: ac has failed, or more than one rectifier has
failed, or the bus voltage is below the Low Load threshold, or Rectifier Shutdown is set to Disabled,
or Rectifier Shutdown is set to Automatic.