System Operation
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
31
Configuration
Set the following parameters.
Parameter
Description
Where to find:
Cells Per String
The number of 2V cells per battery string (for
example: 24 in a 48V nominal system).
SC200: Battery > Battery
DCTools/Web: Batteries
Slope
Bus voltage adjustment rate. Use the value
recommended by the battery manufacturer.
SC200: Control Processes >
Temp. Compensation >
Enable
DCTools/Web: Control
Processes > Temperature
Compensation
Reference Temp
The temperature where no voltage adjustment is
applied. Refer also to Float Voltage on page
Upper Limit
No additional voltage adjustment is made above
this temperature.
Lower Limit
No additional voltage adjustment is made below
this temperature.