SC200 Handbook
92
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
GSM Modem Communications
Connections
The PC modem may be external to the PC (as shown) or internal.
SC200 system controller
PC/laptop with DCTools.
RS232 modem cable (straight-thru). If access to
XS1 is restricted use a DB9 ribbon cable extension
(Farnell part number 869-6411).
GSM modem
Modem
Optional:
SMS text capable GSM cell phone or SMS-Email
Gateway (if available)
SMS text message "P" or "p"
Power status text messages
Alarm text messages
SC200 Setup
Not all modems are suitable. If your modem does not operate correctly check the modem setup
string. Contact your Eaton dc product supplier or Eaton for further assistance. See Worldwide
Support on page
► To enable modem communications
1
Connect to the SC200 with
DCTools
(see details on page
2
Go to
Communications
.
3
Click on
+
to expand
Serial
. Configure the following settings:
Enable Modem:
Enabled
Modem Power Reset:
Optional. If this is enabled, then the SC200 will attempt
to reset a non-operating modem by turning its power
supply off and on using digital output 2.
Modem Set Up String:
The string sent to the modem on reset.
The modem AT command should not be included as it
is automatically sent. The Auto-Answer Rings
parameter is also sent, so it does not need to be
included here. For complete details of appropriate
commands, consult your modem documentation.
Modem Auto Answer Rings: Number of rings before an incoming call is answered.
Setting this parameter to zero disables incoming calls
(the modem can still be used for alarm reporting).