Appendix A
Specifications
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
105
A
p
p
e
n
d
i
x
A
Specifications
SC200 system controller
Communications
USB
Version:
Connector:
1.1 (12Mbits/s)
USB B (female)
RS232
Interface:
Connector:
RS232 (DTE)
DB9M
Ethernet
Interface:
Connector:
Protocols:
10baseT
RJ45
TCP/IP, SNMP, S3P over IP,
http (Web), https (secure Web),
SNTP, Modbus-TCP, Serial
Server
MAC Address:
See details on page
Web browser:
Microsoft Internet Explorer 8 or
later (IE6 is compatible but with
reduced performance), Mozilla
Firefox 3.0 or later.
External modem options
Type:
Operation:
PSTN or GSM
Dial in/Dial out on alarm*
* Can operate as a backup for Ethernet communications.
IOBGP-00, -01 I/O Board
The following specifications apply to a single IOBGP-00, -01 I/O board connected to the SC200
system controller.
Digital Outputs/Alarm Relays (IOBGP)
Number of Digital Outputs/Relays
6 (one also used for Monitor OK alarm)*
Contact Arrangement
One changeover contact per relay
Contact Rating
0.1A @ 60V dc maximum
Connectors
Screwless terminal blocks
Wire Size
0.5 - 2.0mm
2
[20 - 14 AWG]
Maximum Cable Length
20m (65 feet)
Isolation
Relay connections are isolated to 500V dc from all
other circuitry, earth and system common.
* Digital Output 6 is also used as the Monitor Fail alarm relay. It will de-energize if the I/O board