Contactor Configuration
Parameter
Description
Where to find:
LVD Num
Set to the number of the LVD control channel
that will operate this contactor.
In DCTools/Web, number is from first
column of the
Logical LVDs
table.
SC200: See LVD Setup on
page
DCTools/Web: Control
Processes > LVD > Physical
Contactors
Enable
Set to
Enabled
for this contactor to be operated
(connected and disconnected).
If a connected contactor (contacts closed)
is Disabled, it will remain connected
unless the coil is disconnected from the
I/O board or the I/O board loses power.
IOB Number
(On IOB)
Set to the number of the I/O board from the
I/O
Board to Serial Number Mapping
table.
See I/O Board Mapping on page
SC200: Battery > LVDs >
LVD x > Contactors (x-1, x-2,
...) > Edit
DCTools/Web: Control
Processes > LVD > Physical
Contactors
IOB LVD Number
(LVD Connector)
For IOBGP I/O boards, set to:
1, if the contactor is connected to XH4
2, if the contactor is connected to XH5.
See Input/Output Board on page
Type
Set according to the type of contactor:
Normally Open
if contacts are open
when coil voltage is zero.
Normally Closed
if contacts are closed
when coil voltage is zero.
Normally closed LVD contacts require
special system wiring when used to
disconnect the battery.
Smart Alarm Disconnect
An LVD control channel can be set to disconnect if a specified
Smart Alarm
becomes active. For
example, a battery LVD can be set to disconnect if the battery temperature is too high, or a load
LVD can be set to disconnect when
Ah Discharged
exceeds a defined value.
An unnecessary LVD disconnect may occur if
Smart Alarm Disconnect
uses a sensor
which becomes faulty or disconnected.
An unnecessary LVD disconnect may occur if
Battery Time Remaining
is used as a
source for Smart Alarm Disconnect.