System Operation
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
53
Scheduled Sources
Parameter
Setting
SA Num
Type the number (from the
Smart Alarm States
table) of the
Smart Alarm
for
which this source is an input.
Status
Set to
Enabled
.
First Date / Time
Set to the date and time when the
Schedule Source
will activate for the first time
(see the diagram below).
Duration
Set to the length of time that the
Schedule Source
will remain active each time it
activates (see the diagram below).
Interval
Set to the time interval between the start of each activation (see the diagram
below).
Number of
Activations
Set the number of activations.
If set to zero then there is no limit to the number of activations.
Scheduled Sources Operation
Duration
Interval
Active
Inactive
First
Date/Time
Time
1
2
3
4
Activation
number