6 Parameter structure
6.6 Parameter
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives
05/21 MN040058EN
www.eaton.com
143
P00-12
t-Run since Trip
0 h
65000 h
Total operating time of the drive since the last trip
occurred
Displayed in hours, minutes and seconds.
Pressing the UP key on the drive keypad will change
the display from "hours" to "minutes and seconds"
P00-13
Last Fault1 PDP
–
–
Last fault
P00-14
t-HoursRun Enable
0
65000 h
Total operating time of the drive since the last drive
ENABLE signal was applied.
Displayed in hours, minutes and seconds. Pressing
the UP key on the drive keypad will change the
display from "hours" to "minutes and seconds"
P00-15
DC-Link0 Log
0 V
1000 V DC
DC link voltage log
Recording of the most recent 8 samples of the DC
bus voltage prior to a drive trip condition occurring.
The sample interval is 256 ms.
P00-16
Heatsink0 Log
- 20 °C
120 °C
Heatsink temperature log
Shows the last eight heat sink temperature values
before the device was switched off due to a fault.
The sample interval is 500 ms.
P00-17
MotorCurrent0 Log
0 A
2
∙
I
e
Motor current log
Shows the last eight motor current values before the
device was switched off due to a fault. The sample
interval is 256 ms.
P00-18
DC-Link V-Ripple0 Log
0 V
1000 V
DC bus Voltage Ripple Log
P00-19
AmbientTemp0 Log
-20 °C
120 °C
Internal Ambient Temperature Log
P00-20
T-Controlboard
-80 °C
120 °C
Internal ambient temperature of the device,
measured on the control board
P00-21
Input Data1 Value
Input Data 1, Value
Input Data2 Value
Input Data 2, Value
Input Data3 Value
Input Data 3, Value
Input Data4 Value
Input Data 4, Value
P00-22
Ouput Data1 Value
Output Data 1, Value
Ouput Data2 Value
Output Data 2, Value
Ouput Data3 Value
Output Data 3, Value
Ouput Data4 Value
Output Data 4, Value
P00-23
t-Run IGBT in OT
0 h
65000 h
Time elapsed, in which the drive has operated with
a high heatsink temperature
P00-24
t-Run PCB in OT
0 h
65000 h
Time elapsed, in which the drive has operated with
a high temperature at the PCBs (ambient
temperature)
P00-25
Motor Speed
-P-01
P-01
Motorspeed (calculated or measured)
P00-26
MWh Meter
–
–
Energy Consumption MWh Meter (not resettable)
P00-27
Fan Runtime
0 h
65000 h
Run time of the integrated fan (not resettable)
P00-28
Motor Control Software Version
System version
Parameter
Designation
min. value
max. value
Description
Summary of Contents for PowerXL
Page 4: ......