3 Installation
3.6 Electrical Installation
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives
05/21 MN040058EN
www.eaton.com
73
Table 9:
Cable glands that can be used (see figures 44, 45)
The EMC cable gland must be earthed properly – e.g., with a metal lock nut
that is then connected to the PE terminal.
Figure 46: Grounding the EMC cable gland
Figure 47: Example: diagram of EMC gland assembly
→
Make sure that the cable glands have at least an IP66 degree of
protection.
Context
Frame size
Hole size
PG-gland
Metric gland
Control
section
Control
③
FS1
2 x 22 mm
2 x PG 13.5
1 x PG 16
2 x M20
1 x M25
FS2
Power Part
Mains
①
Motor
②
FS1
3x22mm
3 x PG 13.5
3 x M20
FS2
1 x 22 mm
2 x 25 mm
1 x PG 13.5
2 x PG 16
1 x M20
2 x M25
1 2 3 4 5 6 7 8 9 10 11
U
V
W
L1/N L2/N
L3
⏚
⏚