6 Parameter structure
6.6 Parameter
144
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives
05/21 MN040058EN
www.eaton.com
P00-29
NoOfInputPhases
Number of input phases
FrameSize
Construction size
kW/HP
Motor Power
Power@Ue
Device Power at Device Voltage Rating
Device Voltage
Rated operating voltage
DeviceType
Device Type
P00-30
Serial Number
Serial Number of the device
P00-31
Magnetizing current I
q
0 A
100.0 A
Calculated Magnetizing Current
P00-31
Torque current I
d
0 A
100.0 A
Calculated Torque producing Current
P00-32
Switching Frequency
4 kHz
32 kHz
Power stage switching frequency. Higher frequency
reduces the audible ’ringing’ noise from the motor,
and improves the output current waveform, at the
expense of increased heat losses within the drive.
P00-33
FaultCounter Overcurrent
0
65535
Counts, how often “Overcurrent” occurred
P00-34
FaultCounter DC-Overvoltage
0
65535
Counts, how often “DC-Overvoltage” occurred
P00-35
FaultCounter DC-Undervoltage
0
65535
Counts, how often “DC-Undervoltage” occurred
P00-36
FaultCounter Overtemperature
Heatsink
0
65535
Counts, how often “Overtemperature Heatsink”
occurred
P00-37
FaultCounter Overcurrent Brake
Chopper
0
65535
Counts, how often “Overcurrent Brake Chopper”
occurred
P00-38
FaultCounter Overtemperature
Ambient
0
65535
Counts, how often “Overtemperature Ambient”
occurred
P00-39
FaultCounter Communication Loss
0
65535
Counts, how often “Communication Loss” occurred
P00-40
FaultCounter CANopen COM Loss
0
65535
Counts, how often “CANopen COM Loss” occurred
P00-41
FaultCounter Internal Fault (IO)
0
65535
Counts, how often “Internal Fault (IO)” occurred
P00-42
FaultCounter Internal Fault (DSP)
0
65535
Counts, how often “Internal Fault (DSP)” occurred
P00-43
t-PowerOn
Total time for which the drive was powered up since
the day of manufacture.
P00-44
n/a
P00-45
n/a
P00-46
n/a
P00-47
t-FireMode Active
Run time in Fire Mode
P00-47
FaultCounter Fire detected
Counts, how often “Fire detected” occurred
P00-48
ScopeChannel1
P00-48
ScopeChannel2
P00-49
ScopeChannel3
P00-49
ScopeChannel4
P00-50
System Software Version
System Software Version
P00-50
Application Software Version
I/O Controller / Application SW Version
Parameter
Designation
min. value
max. value
Description
Summary of Contents for PowerXL