6 Parameter structure
6.6 Parameter
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives
05/21 MN040058EN
www.eaton.com
147
P-11
V-Boost
0.0 % U
e
100 % U
e
Output voltage of the variable frequency drive at
start with the frequency set with P-32.
After starting, this voltage will increase to the
rated motor operating voltage (P-07) with the value
set in P-33.
See also
section 5.5.1, “Starting single-phase
3 % U
e
P-12
Local ProcessData Source
0
13
Local Configuration of Command and Reference
Sources
0: Terminal Control. The drive responds directly to
signals applied to the control terminals.
1: Uni-directional Keypad Control. The drive can be
controlled in the forward direction only using an
internal/external or remote Keypad
2: Not permissible
Pressing the keypad START button toggles
between forward and reverse.
3: Modbus Control. Control via Modbus RTU
communication.
4: Modbus Control. Ramp times via Modbus
5: PI controller with external actual value
6: PI controller with external actual value and
totalized value of AI1
7: CANOpen (internal ramp times)
8: CANOpen (CANOpen ramp times)
9: SmartWire Device Control and speed ref.
10: SmartWire Device Control and terminal speed
ref.
11: Terminal Control and SmartWire Device speed
ref.
12: Not permissible
13: SmartWire Device Control and speed ref.
Digital input sets enable.
0
P-13
reserved
–
–
–
–
P-14
Password
0
65535
Entry of the password to get access to the
extended parameter set.
The value to be put in is determined by P-37
(default: 101).
Access to Level 2 (extended
→
P-01 to P-59 and
P00-01 to P00-30): P-37
Access to Level 3 (advanced
→
P-01 to P-68 and
P00-01 to P00-50): P-37 + 100
0
Para-
meter
Designation
min. value
max. value
Description
DS
Summary of Contents for PowerXL
Page 4: ......