7 Technical Data
7.1 General rated operational data
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives
05/21 MN040058EN
www.eaton.com
159
Motor feeder
Output voltage
U
2
V
1~ 0 - U
e
Assigned motor output
at 115 V, 50 Hz
P
kW
0.37 - 0.55
at 230 V, 50 Hz
P
kW
0.37 - 1.1
Output Frequency
Range, parameterizable
f
2
Hz
0 - 50/60 (max. 500 Hz)
resolution
Hz
0.1
Rated operation current
I
e
A
4.3 - 11
Overload current for 60 s every 600 s
i
l
%
150
Overload current for 3.75 s every 600 s
i
l
%
175
Switching frequency (double modulation)
f
PWM
kHz
max. 32
Operating mode
V/Hz control (speed accuracy)
±20 %, with slip compensation
Response time (enable IGBT)
t
r
ms
< 10
Brake chopper
only for size FS2
Braking current during continuous operation
%
100 (I
e
)
Maximum braking current
%
150 for 60 s