35
User Manual
MN040024EN
Effective November 2016
DX-NET-ETHERNET2-2 fi eld bus connection
EtherNet/IP for variable frequency drive DE1/DC1
EATON
www.eaton.com
To view the Module Definition window, select the Change button
and the following window will open:
It is highly recommended that the data type be changed from
SINT to INT as follows:
Much of the I/O data to and from the drive are 16-bit word values,
such as motor speed and motor current. This makes viewing and
setting these values much more straight forward. Another option
is to download the Add-On Instruction developed for the DC1/DE1
drive. The AOI creates all I/O tags in the proper data type, such as
BOOL, Bytes and Words. It also handles all the scaling and provides
data in engineering units. The AOI can be used as many times in
your program as the number of drives in the system. The AOI for the
DC1/DE1 drives as well as for all Eaton EtherNet/IP motor control
products can be found on the Eaton website at www.eaton.com.
Select OK to close and save this screen. Then select OK to the New
Module window just created, then Close the Select Module Type
screen.
The DX-NET-ETHERNET2-2 should now be displayed in the Controller
Organizer under Ethernet as shown below:
If you choose to use the Add-On Instruction for the DC1/DE1 drives,
this would be a good time to import it into your project. Complete
instructions for using AOIs is provided with the AOI.