INSTALLING THE PDU
EATON
Powerware
®
225 kVA PDU Installation and Operation Manual
S
164201629 Rev D
www.powerware.com
3−2
5.
Locate the field kit (packed inside of the cabinet). Locate the four 1/2
"
jacking
bolts and install them in the threaded holes in the front and rear supports as
shown in Figure 3-1. Place a floor protector underneath each jacking bolt, and
screw the bolts down against them.
The floor protectors protect the floor from being marred by the jacking bolts.
6.
Close the inside distribution panel doors and secure with screws.
7.
Close the outside doors and secure the latch.
Floor Protector
(Step 5)
4
6 Support
Front Support
4
Jacking Bolt
(Step 5)
Side Support
Cabinet Support
Hardware (Step 13)
Figure 3-1. Removing Shipping Supports
8.
Loosen, but do not remove, the hardware holding the 4
6 supports to the front
and rear supports (see Figure 3-1).
9.
Turn each jacking bolt consecutively, two full turns, until the 4
6 supports clear
the floor by approximately 3 mm (1/8
"
).
W
A
R
N
I
N
G
RISK OF INSTABILITY. Turning the jacking bolts unevenly may cause the cabinet to become unbalanced. To
prevent tipping the cabinet, raise and lower the jacking bolts evenly.
C
A
U
T
I
O
N
CABINET MAY TIP. Raise the PDU cabinet no more than 3 mm (1/8") above the floor (just enough to allow
removal of the 4
6 supports).
10.
After the 4
6 supports clear the floor, remove the hardware loosened in Step 8.
Pull the 4
6 supports out from under the PDU cabinet. Discard or recycle them
in a responsible manner.