INSTALLATION REFERENCE
EATON
Powerware
®
225 kVA PDU Installation and Operation Manual
S
164201629 Rev D
www.powerware.com
A−29
PDU
Output To
Critical
Load
B
AC Input
Output To
Critical
Load
B
A
Output To
Critical
Load
B
Output To
Critical
Load
B
Output To
Critical
Load
B
Output To
Critical
Load
B
PDU Sidecar
(Optional)
Main Input
Breaker CB1
225A
Panelboard
Number 1
225A
Panelboard
Number 1
PDU Sidecar
(Optional)
225A
Panelboard
Number 2
225A
Panelboard
Number 2
Options
NOTE
The PDU is available with options for up to eight 225A subfeed breakers.
Sidecars are available with options for one or two 42-pole 225A distribution panels.
225A Subfeed
Breakers
225A Subfeed
Breakers
Transformer
480V/208V
or
600V/208V
Figure A-23. PDU Subfeed Breaker Output – 480V and 600V Input, and 208/120V Output
Summary of Contents for Powerware 225 kVA Three-Phase Power Distribution Unit