COMMUNICATION
EATON
Powerware
®
225 kVA PDU Installation and Operation Manual
S
164201629 Rev D
www.powerware.com
7−9
7.5
Modbus Register Mapping
7.5.1
Read Input Status
Modbus Function Code 02
Input registers start at 10000.
Register
Name
Value
Format
Unit
11
System normal
1
BOOL
Status
16
PDU Off
0
BOOL
Status
NOTE
Registers 1 – 16 are mutually exclusive.
150
Input AC over voltage
0
BOOL
Status
151
Input AC under voltage
0
BOOL
Status
152
Input under or over frequency
0
BOOL
Status
153
Output AC over voltage
0
BOOL
Status
154
Output AC under voltage
0
BOOL
Status
155
Output under or over frequency
0
BOOL
Status
156
Remote emergency power off
0
BOOL
Status
162
Building Alarm 2
0
BOOL
Status
163
Building Alarm 1
0
BOOL
Status
169
Output overload
0
BOOL
Status
241
Emergency shutdown command
0
BOOL
Status
303
Greater than 106% overload on phase A
0
BOOL
Status
304
Greater than 106% overload on phase B
0
BOOL
Status
305
Greater than 106% overload on phase C
0
BOOL
Status
306
Greater than 125% overload on phase A
0
BOOL
Status
307
Greater than 125% overload on phase B
0
BOOL
Status
308
Greater than 125% overload on phase C
0
BOOL
Status
309
Greater than 150% overload on phase A
0
BOOL
Status
310
Greater than 150% overload on phase B
0
BOOL
Status
311
Greater than 150% overload on phase C
0
BOOL
Status