PDU OPERATING INSTRUCTIONS
EATON
Powerware
®
225 kVA PDU Installation and Operation Manual
S
164201629 Rev D
www.powerware.com
6−19
C
A
U
T
I
O
N
Do not attempt to restart the system after using the REPO until the cause of the shutdown has been
identified and cleared.
2.
To restart the PDU after activating the REPO, deactivate the REPO switch by
inserting the supplied key and rotating clockwise until the red pushbutton
releases (see Figure 6-11). To remove the key, rotate the key back to the vertical
position and follow the procedure in paragraph 6.4.2.
Deactivated
Unlock pushbutton to release
Activated
Pushbutton locked into place
Figure 6-11. REPO Operation
6.4.6
Shutdown
To shut down the PDU:
1.
Unfasten the front door latch and swing the doors open.
2.
Shut down the load equipment according to the manufacturer’s recommended
shutdown sequence.
Load equipment may be turned off at the equipment or at the circuit breakers on
the PDU.
3.
Turn off all the panelboard main input circuit breakers or subfeed breakers.
4.
Open the PDU
main input breaker (CB1) directly or use the control panel.
5.
To remove power from the PDU completely, turn off utility power to the PDU.
6.
Close the outside doors and secure the latch.