35
Instruction Booklet
IB022018EN
Effective July 2020
Instructions for the installation and
EATON
www.eaton.com
Figure 64.
Coupling
Connector
Note:
The Output Compartment
can accommodate up to
three connectors, or two
connectors and a surge
arrester.
XGIS
Tank Wall
Cable Bushing
Output Bushing
Bracket
Coupling
Connector
Cap
Space
for
Cable CT
Tee
Connector
Surge Arrester
Separable power cable connectors.
Figure 65. Cable separable connectors in 2000 A or 2500 A
cable compartments.
The separable connectors include a shield layer that is used to
ground the exterior of the connectors. The ground wires must be
fastened to the compartment ground bus. This will ensure the outer
surface of the separable connectors are at ground potential.