10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.2 EtherCAT
PXR Electronic trip unit
01/21 MN012005EN
www.eaton.com
113
2087
210D
Counter - I
r
tripping
–
1
2088
210E
Counter - I
g
tripping
–
1
2089
210F
Counter - trips total
–
1
208A
2110
Counter - test mode tripping
–
1
208B
2111
Counter - number of openings via the communica-
tion interface
–
1
208C
2112
Counter - external actuation
1)
–
1
208D
2113
Time of last actuation
(year, month, day, hour, minute, second)
–
–
208E
2114
Operating time
2)
in minutes
min
1
208F
2115
Operating time
2)
in hours
h
1
2090
2116
Operating time
2)
in days
d
1
2091
2117
Residual life
3)
points
–
1) An external actuation is a switching operation that is not initiated by the trip unit, such as manual switching,
switching via an externally wired remote operator or the actuation of a push-to-trip button.
2) The operating time counter will start as soon as the device is energized, either autonomously or through an
external power supply.
3) 0 points
≙
100 % residual life
10.000 points
≙
0 % residual life
Conversion formula: Residual life expressed as a percentage = 100 - (point value / 100)
Index (Hex)
Object
IEEE
floating
point
Fixed
point (FP)
Description
(Values in brackets reflect the American
notation.)
Unit
Scale
factor (FP)