10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.2 EtherCAT
118
PXR Electronic trip unit
01/21 MN012005EN
www.eaton.com
In setting group 0, the maintenance mode setting (index 2008) can be
divided into two parts. The high byte is read only and is used for the status
indication of the maintenance mode, the comprehensive results of the
maintenance mode rotary switch, the secondary terminal and the
communication settings. The low byte can be configured and is used to
indicate the maintenance mode settings via the communication port.
The respective protection settings may vary according to the size, type and
rated operational current of the release.
200B
0
0x0001
Direction of inco-
ming supply
R/W
Encoded
0: forward
1: reverse
Note:
only available on the PXR25
–
200C
0
0x0001
Sign convention
R/W
Encoded
Sign convention:
0: IEC
1: IEEE
2: IEEE old
–
200D
Power demand
window
R/W
Encoded
Power demand:
0: fixed
1: sliding
–
200E
Power demand
interval
R/W
Encoded
Power demand:
5 - 60 min (1 min increments)
–
2011
Configuration of
relay 1
R/W
Encoded
Configuration of relay 1 and relay 2:
–
2012
Configuration of
relay 2
R/W
Encoded
–
2014
Phase sequence -
phase L1 (A)
R/W
Encoded
Phase L1 (A)
0: counterclockwise
1: clockwise
–
2017
0xBCC
Alarm - Residual
Life
R/W
Encoded
Range: 50 - 100, step size 1, default value: 75
Alarm level value 100
≙
0 % residual life
Alarm level value 75
≙
25 % residual life
Formula for conversion:
Alarm level expressed as a percentage
= 100 - point value
–
Index
(Hex)
Bit
field
Mask
field
Setpoint name
R/W
Format
Description or value
Unit